Single-Phase Surge Protection
Designed to suppress and discharge transient surges on 240V single-phase AC power lines.
The SP240 Series DIN Rail Surge Protection Device (SPD) is designed for 240V single-phase power lines, with seven models offering maximum discharge current ratings from 10kA to 120kA.
The SP240 Series provides surge protection for single-phase AC power distribution systems. The devices are connected in parallel with the protected loads to suppress and discharge transient overvoltage and surge currents.
The original technical brochure lists Type D, Type C and Type B protection classifications for 240V AC power systems. Available models range from SP240-10KA/2 to SP240-120KA/2.
The series uses a modular design with a visual status indicator, thermal breaker and built-in overcurrent fuse protection. The indicator displays green under normal operating conditions and red when deterioration is detected.
Designed to suppress and discharge transient surges on 240V single-phase AC power lines.
The modular surge protection device is designed for installation on a 35mm DIN rail within a distribution board.
The built-in indicator shows green for normal operating condition and red when the device has deteriorated and requires replacement.
The original brochure specifies a thermal breaker and built-in overcurrent fuse protection.
Nominal discharge current (In) and maximum discharge current (Imax) are specified separately, both using an 8/20µs surge current waveform.
| Model | In (8/20µs) | Imax (8/20µs) | Up |
|---|---|---|---|
| SP240-10KA/2 | 5kA | 10kA | ≤1.0kV |
| SP240-20KA/2 | 10kA | 20kA | ≤1.2kV |
| SP240-40KA/2 | 20kA | 40kA | ≤1.5kV |
| SP240-60KA/2 | 30kA | 60kA | ≤2.0kV |
| SP240-80KA/2 | 40kA | 80kA | ≤2.2kV |
| SP240-100KA/2 | 50kA | 100kA | ≤2.5kV |
| SP240-120KA/2 | 60kA | 120kA | ≤2.5kV |
In = Nominal Discharge Current; Imax = Maximum Discharge Current; Up = Voltage Protection Level. All values are from the original manufacturer specification.
| Product Type | DIN Rail Surge Protection Device |
|---|---|
| Power System | Single-Phase AC |
| Operating Voltage (Un) | 240V |
| Maximum Continuous Operating Voltage (Uc) | 285V |
| Protection Classes Listed | Type D / Type C / Type B |
| Protection Mode | L-PE and N-PE (2P) |
| Response Time | Less Than 25ns |
| Leakage Current | ≤20µA |
| Status Indicator | Green: Normal / Red: Deterioration |
| Operating Temperature | -40°C to +70°C |
| Relative Humidity | Less Than 90% |
| Enclosure Material | Flame-Retardant ABS |
| Mounting | 35mm DIN Rail |
| Connection | Parallel Connection to Power Lines |
The original installation instructions specify mounting the unit on a 35mm DIN rail and connecting it in parallel with the incoming power lines in a distribution board.
The incoming power source must be isolated before electrical connections are made. Live, neutral and protective earth connections must follow the terminal markings and original installation diagram.
The manufacturer recommends regular status checks. A green indicator denotes normal condition, while a red indicator means the device has deteriorated and requires replacement.
Both original technical images are retained below, covering the model ratings, product information and installation instructions.